Using AI to Do an Engineer’s Work

Steven Turner, ConsultantColumns, Relay Column, Summer 2026 Columns

Recently, I challenged a proprietary AI platform to solve a simple protection problem: Use a CO-9 overcurrent relay to provide backup protection for a 150 MVA transformer; the high-side voltage is 230 kV. Plot the characteristic of the CO-9 versus the transformer damage curve. This was not an especially difficult problem to solve. I wanted to see if it would …

On Voltage Dividers: Applications and Hazards

Michael Labeit, RESA PowerColumns, In the Field, Summer 2026 Columns

Voltage dividers are simple devices consisting of series circuits that produce two or more lower voltages from a single source voltage via resistances. This is possible because of this mathematical fact: Given a series circuit with multiple resistances, the sum of the absolute values of all voltage drops across each resistance will equal the source voltage.  This fact is illustrated …

Mascots and Electrical Safety Culture Engagement: Are You Reddy and Willie(ing)?

Ron Widup, Vector PowerColumns, NFPA 70E and NETA, Summer 2026 Columns

OK, let’s be honest. When you pull NFPA 70E off the shelf, it’s not exactly something you look forward to reading for entertainment. Yes, it matters. (It matters a lot!) But it’s not built to grab your attention or stick with you. And that’s not a knock on the standard. Consensus standards like NFPA 70E serve a clear purpose: to …

NETA: Standing for a Higher Standard

Dan Hook, CBS Field Services, NETA PresidentColumns, President's Desk, Summer 2026 Columns

This Summer edition of NETA World arrives at a pivotal moment for our industry. Demand for electrical testing and commissioning has never been higher, expectations have never been greater, and the pace of change continues to accelerate. Across every segment, from data centers to grid modernization, we are being asked to do more, move faster, and deliver with absolute precision. …

Substation Safety: Are You Rock Solid?

Jacob Rioux, Hood Patterson & DewarColumns, Spring 2026 Columns, Tech Tips

Substation design typically calls for two to six inches of aggregate (crushed rock) as a top layer upon completion of construction. This layer serves several purposes, including improved vehicle access, reduced erosion, and suppression of vegetation. Another significant function of this layer is to provide personnel safety by increasing the allowed (maximum permissible) touch and step potential values versus native …

Acceptance Testing and Commissioning

Morgan Gieni, Magna IV EngineeringColumns, Spring 2026 Columns, Tech Quiz

Electrical equipment is selected by a design engineer for a specific purpose. This includes operating within the manufacturer’s specifications, as well as how it functions within the system.  For newly installed equipment, it is important for NETA Certified Technicians to critically verify that all aspects of the equipment work as intended to ensure proper and reliable operation of the electrical …

Safety Tips for Circuit Breaker Maintenance and Testing

Paul Chamberlain, Asplundh Engineering Services, LLCColumns, Safety Corner, Spring 2026 Columns

Breaker testing and maintenance can expose personnel to many types of hazards. Mitigating them can be achieved in various ways. First, it must be verified that the personnel are qualified to perform the required tasks. The person doing the work must recognize and understand the hazards that may be encountered while performing the tasks.  To better understand the many hazards …

Using the KD-10 to Provide 78 Out-of-Step Tripping Protection for a Large Generator

Steven Turner, ConsultantColumns, Relay Column, Spring 2026 Columns

Typically, multi-function numerical generator protection relays are now used to provide out-of-step tripping (OST) for large unit-connected generators. However, some users prefer to maintain older existing infrastructure, such as electromechanical relays. 78 OST protection must meet PRC-026-2 Criterion A of Attachment B requirements as follows: PRC-026 Criterion A of Attachment B indicates that a 78 impedance-based out-of-step protection function should …

On Transformers with Electrostatic Shields

Michael Labeit, RESA PowerColumns, In the Field, Spring 2026 Columns

If you’ve worked on transformers in renewable energy circuits, as I have for the past six months, you’ve likely seen many—perhaps most—equipped with electrostatic shields, grounded copper or aluminum sheets wedged between the high- and low-side windings. The existence of these shields inside transformers is normally (but not always) readily identifiable via the unit data plates (Figure 1). Some affirm …

The Most Dangerous Electrical Task You Do Every Day

Ron Widup, Vector PowerColumns, NFPA 70E and NETA, Spring 2026 Columns

We work around electricity every day.  We are exposed to hazards every day.  But what’s the most dangerous task YOU do every day? DANGEROUS TASKS The Starting Point: Turn It Off! My guess is you treat switching operations like surgery—plan the task, determine the proper shutdown sequence, see which loads are affected, check the one-line diagrams, verify the labels, double-check …