Utility generation is held to high standards to ensure consumers receive clean, reliable power. However, industrial facility owners must take care to limit their impact on the grid. As NETA Certified Technicians, we must be aware of the required quality standards as they pertain to both utility and industrial applications.
1. In IEEE Std. 519, Harmonic Control in Electric Power Systems, where is the strict boundary line located where a utility must provide clean voltage, and where an industrial facility must limit the current harmonics they inject back into the grid?
a. At the main utility generator terminals
b. At all primary VFD terminals
c. At the panel feeding individual variable speed drives inside the user’s facility
d. At the point of common coupling, where the utility connects to the industrial customer
2. Why do power quality standards treat utilities and industrial plants differently regarding harmonics?
a. Utilities are responsible for controlling current harmonics, while industrial plants must control voltage harmonics.
b. Industrial plants only care about voltage harmonics because they do not use electronic equipment.
c. Utilities must control voltage harmonics, while industrial facilities must control current harmonics.
d. Utilities do not have to follow any harmonic standards, but industrial plants do.
3. Industrial facilities often run heavy machines, such as arc furnaces and large motors, that start and stop rapidly, causing lights to dim and brighten. Which standard and metric are used by utilities to test and measure this effect?
a. IEEE 1547 using Total Rated Demand Distortion (TDD)
b. IEEE 1453 using Short-Term Flicker Severity and Long-Term Flicker Severity
c. NEMA MG1 using the Motor Derating Factor
d. NFPA 70E using Incident Energy Analysis
4. According to IEEE 519, how does the utility’s short-circuit ratio (Isc/IL) affect an industrial site’s allowed current distortion limits?
a. A higher short-circuit ratio means the grid is stronger, allowing the site to operate with higher percentages of current harmonics.
b. A higher short-circuit ratio means the grid is weaker, requiring the site to operate with lower percentages of current harmonics.
c. The short-circuit ratio only matters for utility generation and has no impact on current distortion limits for a site.
d. A lower short-circuit ratio allows the owner to ignore all high-frequency harmonic limits.
5. How does power quality data collection on a site differ when comparing requirements from utility standards versus collecting data while troubleshooting using a power quality meter on a site?
a. Utility measurements are taken at higher voltages and require larger meters.
b. Utility measurements capture large power consumption and require way more memory.
c. Higher voltage means lower current. Current probes within a site distribution network must be large primary-current-rated sensors.
d. Utilities require continuous, highly accurate 10-minute-average windows for at least a week, while industrial troubleshooting often uses fast, millisecond-level snapshot triggers.
Which standard specifically states how utility-scale generation (like wind farms, solar farms, or traditional power plants) must ride through grid disturbances and control voltage, which differs from industrial consumer standards?
a. IEEE 519
b. IEEE 1547
c. NEC Article 430
d. OSHA 1910
What is the likely root cause difference between unbalance in utility generation versus an industrial network?
a. Utility unbalance is caused by three-phase generators; industrial unbalance is caused by running too many lights.
b. Utility unbalance is usually due to unevenly distributed single-phase customers on the grid lines; industrial unbalance is usually due to large, unequal single-phase loads or failing equipment inside the user’s facility.
c. Utilities never experience unbalance because transformers automatically fix it before it reaches a user’s facility.
d. Utilities are typically unbalanced due to an unstable generator, and industrial unbalance is caused exclusively by using solar panels on the roof.

Morgan Gieni, CET, PSE, is the Technical Support Lead Technical Field Services (TFS) at Magna IV Engineering. He is an ASET Certified Engineering Technologist and a NETA Level 4 Certified Senior Technician and is on NETA’s Technical Resource Committee.